Continuously monitored electrostatic grounding to ensure safe loading and unloading of flammable liquids and powders from:
Road trucks
Rail wagons
Containers
Drums
Bags
Single and two channel versions are available allowing concurrent grounding of two similar or two various objects in vapour and dust environments.
Continuous monitoring of grounding quality
Indication of false ground
Simple to install and use
Isolated clamp holder
Robust construction
Infra-red IrDA communication available
Wide ambient temperature range -55 °C to +60 °C
- Environment:
Protection II 2G Ex d ib [ib] IIB T4 Gb
II 2D Ex ib [ib] tb IIIC T130°C Db
Certificate FTZÚ 09 ATEX 0059X
Ingress Protection IP65
Ambient Temperature -50 °C to +60 °C
- Power Supply:
Rated Voltage Range 20-253 Vdc / Vac
Power Consumption 10 W
Cable Glands M20x1.5
Cable Type Ø 6.1 to 11.7 mm
- Physical Parameters:
Dimensions 325 x 334 x 124 mm
Weight 10.2 kg 10.9 kg
- Output:
Indication Green and Red LED lights
Relay 2 per channel
voltage free contacts
COM, NO and NC
Minimum load 10 Vdc / 0.1 A
Maximum load DC 230 Vdc / 0.25 A
40 Vdc / 3 A
Maximum load AC 230 Vac / 3 A
Cable Glands M20x1.5
Cable Type Ø 6.1 to 11.7 mm
IS Parameters
Maximum voltage UM 50 Vdc
Maximum current 0.2 A
Straight cable with clamp -50 °C to +60 °C
Arctic cable with clamp -55 °C to +60 °C
Spiral cable with clamp -30 °C to +60 °C
Cable Length 10 m(standard)
up to 120 m on request
Self-retracting reel 15 m cable with clamp
-20 °C to +60 °C
Clamps made from stainless steel with copper points.
Local Language versions of front plate available.