Single Channel Gas Detector Control Panels
Selection of Enclosure Types and Sizes
Our PST owned brand, Status Scientific Controls have manufactured a range of high quality single and multi-channel gas detector control panels which are used throughout the world in various different industries.
Single Channel Control Panels
The MCU1 is a single-channel, wall-mount, monitoring and control unit for use in a safe area where there is no risk of the presence of potentially explosive gases.
- Integral sensor options comprise CO2 (Infrared), oxygen, or a wide range of toxic sensors.
- Can be used with the full range of Status Scientific Controls fixed gas detector heads – certified types require use of an integral safety barrier.
- Green, amber and red flashing indicators in lens section.
- Alphanumeric display with backlight.
- Full calibration menu via external push buttons.
Size (nominal) ‘mm’: 249 x 268 x 200(MCU1), 475 x 300 x 208(MCU3), 475 x 538 x 208 (MCU4)
Weight (approx): 4Kg (MCU1), 16Kg (MCU3), 30Kg (MCU4)
Operating Temperature: -10ºC to +50ºC
Storage Temperature: -20ºC to +50ºC
Humidity Range: 0 to 95% R.H. Non-condensing
Input Voltage: 24V DC, or 120/230V AC 50/60 Hz Tolerance ± 10%
Environmental Rating IP65
Display: Backlit 240 x 64 dot Liquid Crystal Display (LCD) (x2 for MCU4)
Keyboard: 8 button multifunction keypad (x2 for MCU4)
LED Indications:
- Red Indicates alarm condition
- Green Indicates power ON (flashes when powered from int. batteries)
- Yellow Indicates fault condition
Number of channels: 16 max
Signal Inputs 16 Max:
- 4-20mA Current Loop from 24V source
- 4-20mA Current Loop sink to 0V
- 3-Wire Pellistor Systems
- DC Voltage Input
Analogue Output: 4-20mA Current source proportional to detected signal. 4-20mA Current sink proportional to detected signal. 1-5V Voltage output proportional to detected signal.
Channel relays, 3 per channel: 1 relay assigned to each alarm level (low, medium and high)
Contacts: Double Pole Changeover Contacts (voltage free)
Rating: 5A 240V AC
2 – Common Outputs: Output one for external audible alarm (200mA maximum)
Output two for external visual alarm (200mA maximum)
External Reset: Connection for normally open switch contacts (5V max present at terminals).
4 – Common Relays (MCU3/4):
- 1 Relay assigned to each alarm level (low, medium, high)
- 1 Relay designated as fault relay
- Double Pole Changeover Contacts (voltage free)
- 8A 240V AC
Batteries: Sealed lead acid battery type 2 x 12V 1.2Ahr